CPT-1200 CT PT Analyzer
CPT-1200 CT/PT ANALYZER is mainly used for field testing of P class CT and PT.
Description
CPT-1200 CT/PT ANALYZER is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, Degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopt LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
Test Functions
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
| 1. Magnetization Curve | 1. Excitation Characteristic Test |
| 2. Transformation Ratio Test | 2. Transformation Ratio Test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Withstand Test of Power Frequency Alternating Current |
| 5. Current Injecting | 5. Degauss |
| 6. Degauss | 6. Calculation of Knee Point Value |
| 7. Withstand Test of Power Frequency Alternating Current | 7. Actual Secondary Load Test |
| 8. Automatic Calculation of Excitation Knee Point Value | 8. Resistance Test |
| 9. Actual Secondary Load Test | |
| 10. Resistance Test |
Technique parameters
| Power Supply: | AC220V±20V, 50~60Hz |
| Power Supply Output Waveform: | Sine Wave |
| Single Machine Output Voltage of Excitation Characteristic: | 0~2500V |
| Excitation Output Current: | 0~20 A |
| Single Machine Output Current of Transformation Ratio Test | 0~600 A |
| CT ratio measurement range | 5~25000A/5A(5000A/1A) |
| PT ratio measurement range | 1~500KV |
| Load Range | 5~1000VA |
| Resistance measurement range | 0.1~300Ω |
| Error: | ≤0.5%(0.2%*Reading+0.3%*Range) |
| Operating Temperature: | -10℃~+40℃ |
| Relative Humidity: | <90RH% |
| Altitude | ≤1000m |
| Overall Dimension | 400 *200 * 260(mm) |
| Weight: | ≤23 Kg |
| No. | Name | QTY |
| 1 | Host | 1 |
| 2 | Test Wire (with clamps) | 2 |
| 3 | Test Wire (with alligators) | 2 |
| 4 | Ground line (with alligator) | 1 |
| 5 | Power cord | 1 |
| 6 | Fuse | 5 |
| 7 | Printing paper | 2 |
| 8 | Inspection report | 1 |
| 9 | Instruction manual | 1 |
| 10 | Certificate | 1 |