CPT-1300 CT PT Analyzer

CPT-1300 CT PT Analyzer

CPT-1300 is new product created after widely adopt customers’ advices and deep theoretical study.

Description

 

CPT-1300 is new product created after widely adopt customers’ advices and deep theoretical study. It is based on the automatic FA Series Transformer Tester General which is produced by our company that is widely acclaimed and applied. The adoption of high-performance DSP and ARM, advanced manufacturing technology ensure a stable and reliable product performance, full-featured, high degree of automation, high efficiency, in the domestic leading level, they are the professional testing equipment for transformer check in power industry.

 

Product characteristics

1. Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.

2. Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.

3. Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test

4. Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 30KV.

5. Friendly interface beautiful, all Chinese graphic interface

6. The instrument can store 2000 groups of test data that won’t be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.

7. Test is simple and convenient, one-click can complete tests of CT secondary resistance, excitation, ratio and polarity.

8. Easy to carry, because the weight is less than 9KG.

 

Technique parameters

Usage Class P/TP CT & VT
Output 0~180Vrms,12Arms,18A(peak value)
Voltage measurement accuracy ±0.05%
CT Ratio Range 1~30000
accuracy ±0.05%
PT Ratio Range 1~30000
accuracy ±0.05%
Phase Range ±5min
accuracy 0.5min
DC resistance Range 0~300Ω
accuracy 2%±2mΩ
Burden Range 0~300VA
accuracy 2%±0.2VA
Power supply AC220V±10%,50Hz
Environmental Conditions Operating temperature ::-10οC~50οC,Humidity :≤90%
Weight and Dimensions Dimensions:340 mm×300 mm×150mm,Weight<9kg

No. Product Name QTY
1 Host 1
2 5M test wire (red, black) 1
3 5M test wire (yellow, black) 1
4 20M test wire (green, black) 1
5 5M ground wire 1
6 Power cord 1
7 Terminals 12
8 Alligator clips 12
9 10A fuse 5
10 Software Disk 1
11 Printing paper 2
12 Operation manual 1
13 Inspection report 1
14 Certificate 1

Hot Tags: CPT-1300 CT PT Analyzer, China CPT-1300 CT PT Analyzer manufacturers, suppliers, factory, Ct Pt Analyzer, Cpt 1100 Ct Pt Analyzer, Cpt 1200 Ct Pt Analyzer